DSI732 - Dual Isolator

Product Diagram

The DI732 combines two fully independent isolator channels in one housing. The inputs feature separate 19Vdc/22mA auxiliary supplies to drive 3-wire or loop powered field transmitters.

All inputs and outputs are coding plug configurable for the most common process signals. Factory default is 4-20mA. Final calibration can be trimmed by using the front accessible SPAN (S) and ZERO (Z) potentiometers. The optional alarm point on channel 2 is also set by potentiometer utilising the adjacent test socket.

The DI732 can be used in a number of ways:

-Two channel isolation and any mix of signals. -Isolation of two 4-20mA field transmitters -Signal splitting (one input and two isolated outputs).

The wide swing DC/DC converter allows for two power supply ranges: 10-60Vdc (16-42Vac), 80-280Vac (80-300Vdc). Isolation is 2kVrms between all 6 ports. Connections are done via unpluggable screw type 8-way terminals.

Attachments

 
 

Most drawings are supplied in PDF format. Portable Document Format is used to present documents in a manner independent of application software, hardware, and operating systems.

 

Lead Time for a Traditional Product

 

Traditional products usually contain the same functionally as standard and premier products but have a different connection, part number or specifications. Traditional products are still available as a service to our customers that have them specified in their plants. Delivery is typically 7 days.

Stock Variants

 
Stock variants usually ship in 1 day.
 
DSI732-100
Power Supply 80-300Vdc / 80-280V 50/60Hz
Input 1 Link Selectable, Set: 4-20mA, Response: 500mS
Output 1 Link Selectable, Set: 4-20mA
Input 2 Link Selectable, Set: 4-20mA, Response: 500mS
Output 2 Link Selectable. Set: 4-20mA
CH2 Alarm Not fitted
DSI732-200
Power Supply 16-42Vac 50/60Hz (10-60Vdc)
Input 1 Link Selectable, Set: 4-20mA, Response: 500mS
Output 1 Link Selectable, Set: 4-20mA
Input 2 Link Selectable, Set: 4-20mA, Response: 500mS
Output 2 Link Selectable. Set: 4-20mA
CH2 Alarm Not fitted

Order Processing

 
Information

APCS makes and customises products according to a customers order. Upon receipt of the customers order the following information is required before manufacture, allocation or deliver until full details are given, these include;

  1. Identity of purchaser. Company name, ABN (Australian companies), street address and accounts email address.
  2. Required delivery address.
  3. Full part number and calibration detail required to manufacture items.
  4. Total on purchase order to include delivery charges. Orders received with missing information will be entered and marked to indicate missing details and returned to the customer for correction or approval.

Compliance with the above ensures that your items are manufactured and delivered according to the required specifications.

Standard delivery times commence after the order has been approved for processing.