Select products that include an Alarm function.
Select products that include an Alarm function.
The alarm module measures the process variable using the appropriate input circuit for the probe or signal type and compares it with a trip point value to determine when to switch.
Main factors to consider when choosing a alarm module are;
Many trip alarms have a dead band adjustment. Dead band (DB) is a common term for relay hysteresis and is usually expressed as percentage of span (%DB).
Dead band does not interfere with the ON switching of the relay. Looking at the direct action example below, we see that dead band is the change of input required to turn the relay OFF.
Alarm Dead Band
Lets follow the input path on the diagram. The input begins below the set-point adjustment. The output (relay) only switches ON after the input goes above the set-point.
The input continues to vary above and below the set-point however the output (relay) remains ON until the input falls below the dead band adjustment.
The input now varies above and below the dead band adjustment, however, as we can see, the relay can only be switched ON if the input returns above the set-point.
Dead band may be easier to understand if units are introduced. Lets use an example process where the level of a water tank is monitored.
The set-point is set to comfortable operating water level of 10m. The dead band is set to a minimum water level of 8m. With these settings the outlet valve controlled by the alarm allows water to exist the tank only open if the water level rises above 10m, and will close if the water level falls below 8m. If we wanted to reduce the minimum water level to 6m then we would need to increase the dead band.